No Outage Inpsections - Which Tools Are Best for Medium Voltage Electrical Inspections

by Don Genutis

Although there are many useful electrical ‘on-line’ predictive maintenance technologies available to assess equipment condition, this article will outline and discuss the most effective tools for determining the condition of medium and high voltage equipment. A brief application summary is included for each technology in order to enhance your understanding or, if you are already familiar with the technologies, to serve as a review.

Visual Inspections are very useful but may be limited due to equipment construction. However, it is always recommended to conduct thorough visual inspections in conjunction with any of the other ‘no-outage’ technologies. Visual inspections may indicate unusual conditions that other technologies may not directly detect.

Infrared (IR) technology is primarily used to detect conductor problems and can be useful for inspecting any equipment where connections are visible. It is important to realize that insulation problems rarely create a detectable temperature rise, so other technologies should also be employed. IR is probably the best on-line tool for detecting low voltage problems.

Partial discharge (PD) testing using electromagnetic signal detection is very useful in identifying problems within switchgear, cables, dry-type transformers and other devices. PD testing is not as effective as Airborne Acoustic or Corona Camera surveys when inspecting “open” constructed equipment. A new handheld PD detector (shown in Figure 1) has been developed that combines ultrasonic and electromagnetic sensor technologies into one easy-to-use instrument which allows medium voltage insulation to be surveyed for defects in an efficient and cost-effective manner.

Partial discharge detection


Airborne Acoustic (AA) or ultrasonic listening can be useful in detecting direct line-of-sight surface insulation problems or when the acoustic signal escapes the equipment enclosure through openings. One advantage of using ultrasonic inspections is that surveys can be conducted quickly.

The Corona Camera detects direct line-of-sight surface insulation or conductor problems very effectively by producing an image of the problem that is normally invisible during daylight conditions. This technology is perhaps the best for outdoor substations or high voltage applications, but also supplements the other no-outage technologies by providing visual proof of surface problems. Just as every apparatus with connections should be scanned with IR, all medium & high voltage equipment should be scanned for Corona.

Oil/Gas sampling and analysis is an effective tool to indicate both the condition of the insulation and the condition of the equipment. Unfortunately, solid insulation cannot be sampled in the same manner, so other on-line technologies must be employed to evaluate equipment constructed with solid dielectrics.

Comparing the No-Outage Technologies

Remember the old saying - “a picture is worth a thousand words”? Below we will display the differences in some of these technologies pictorially to better help identify their differences.

First, we should briefly explain the differences between two popular inspection methods, infrared and partial discharge technologies. Infrared technology detects heat that is generated by current flow or amperage related problems that are often caused by loose connections. So, infrared detects the condition of the conductor. Partial discharge, ultrasonic and corona surveys detect voltage problems that occur from the partial failure of the insulation. So, these technologies detect the condition of the insulation. In order for partial discharges or corona to occur, typically voltages greater than 2,000 volts must be present. Therefore, these technologies are not effective for low voltage applications.

Now, back to the pictures. We created simple, surface discharges in the laboratory by applying an AC hypot to an unshielded medium voltage conductor that was placed upon a ground conductor. We then performed several types of tests as shown in Figures 2-6.

test set up

corona detection

infrared image

pd test results

 

Magnitude vs. time and magnitude vs. frequency

 


What conclusions can be made from this simple experiment and our previous knowledge of these technologies?

• Infrared is the best tool for low voltage equipment assessment. This should be a “minimum” annual test requirement, especially for low voltage equipment.

• For medium voltage switchgear and dry-type transformers that have surface tracking or corona problems, the Ultrasonic tester provides a quick and relatively inexpensive solution that will detect many problems.

• A Partial Discharge test set using a capacitive sensor can detect “deep” or non-surface insulation defects in medium voltage switchgear and dry-type transformers and should be used to supplement the ultrasonic test set in order to detect additional problems.

• A Partial Discharge test set using a high frequency current transformer is the best tool to detect cable, termination and splice problems

• A Daylight Corona camera is excellent for pinpointing surface discharges in medium voltage equipment and is the best tool for high voltage equipment

Conclusion

So what is the “best” No-Outage technology? The answer is the one that will detect the problem. While none of the technologies discussed in this article can single-handedly detect every type of problem, by employing all of these technologies as part of an annual predictive maintenance program, many problems will be detected and many failures will be prevented. The matrix shown in Figure 7 has been created to help identify the best “No-Outage” technologies available for various types of electrical equipment.

No Outage Test Matrix

Don Genutis received his BSEE from Carnegie Mellon University, has been a NETA Certified Technician for 15 years, and is a Certified Corona Technician. Don’s technical training and education is complemented by twenty-five years of practical field and laboratory electrical testing experience. Recently, Don co-founded and acts as President of No-Outage Electrical Testing, Inc. a Group CBS affiliate that focuses on new inspection technologies that are performed while the equipment remains in service. He can be reached at DGenutis@groupcbs.com  or 813-752-6051.

 

 

Comments (1)

  • Hello Don,

    I happened to come across your article while researching various NDT technologies related to electrical equipment. I found your article to be very informative, especially the Partial Discharge section - this is a technology that I was not familiar with.

    Another technology on the market today that can help reduce electrical downtime is the “Delta T Alert”. This patented device magnetically attaches to your electrical enclosure covers and monitors the delta t between the interior of the enclosure and the ambient temperature of the room in which the enclosure is located. The Delta T Alert is than configured to collect data on a daily basis at specific time intervals and this data is then transmitted to an onsite computer for analysis and trending.

    Please feel free to check out the website at http://www.deltatengineering.com

    Thanks,

    Fred Baier, Level 3 Thermographer - Infraspection Institute

    Delta T Engineering

    1) Posted 11:18 am, 04 October 2010 by Fred Baier

Have your say

Comments are moderated prior to publication.
Please fill out the fields below.
Email addresses will never be published.

Comment guidelines

You can use basic HTML (a, strong, em, blockquote).
Links automatically use the nofollow attribute.
Off-topic or inappropriate comments will be edited or deleted.

Knowledge Base Articles
Related Publication
ReliabilityWeb on Flickr

Advertisement